        Selection and Installation of Lightning Arresters for Transmission Lines

        Author: Click:981 Time:2022-09-23

        Thunder and lightning are common natural phenomena. In recent years, the shunt of lightning current will change. From the lightning protection test, some lightning currents show that when the zinc oxide arrester valve is affected with damp or the environm

        Thunder and lightning are common natural phenomena. In recent years The shunt of lightning current will change. From the lightning protection test, some lightning currents show that when the zinc oxide arrester valve is affected with damp or the environmental conditions continue to deteriorate, the breakdown of transmission lines caused by lightning strikes is also increasing, which not only affects the normal operation of equipment, but also greatly affects daily production and life. Lightning stroke has become the main factor affecting the safe and reliable operation of transmission lines.

        In order to reduce the lightning strike fault of transmission lines, various comprehensive lightning protection measures have been taken, such as reducing the grounding resistance of towers, improving the insulation level of lines, adopting negative angle protection, and erecting coupling ground wires, which have achieved certain results. But for some lines distributed in high soil resistivity. It is difficult to reduce the grounding resistance of the tower, and there is still no good countermeasure to prevent the line fault caused by shielding lightning.

        At present, the line type synthetic insulating zinc oxide arrester has been widely used abroad for lightning protection of transmission lines, and has achieved good results. With the continuous development and progress of our science and technology, our country has also begun to research and develop line arresters. At present, line arresters have been widely used in the power sector. In power distribution lines, the common lightning arresters are: valve type lightning arresters, tube type lightning arresters, zinc oxide lightning arresters, etc. The low-voltage distribution system advocates the selection of low-voltage zinc oxide lightning arresters. The resistance of zinc oxide valve blade is very high under normal operating voltage. Only micro ampere leakage current can be passed. However, when the powerful lightning current is out of date, it shows a very low resistance, which makes it quickly leak to the earth, realizing the purpose of voltage limiting and shunting. The residual voltage on the valve blade almost does not change with the passing current, and it is always maintained at a voltage lower than the impulse test voltage of the protected electrical appliances, so that the insulation of the equipment is protected, and the original insulation state is restored after the lightning flows.

        Zinc oxide arrester has excellent nonlinear volt ampere characteristics. The residual voltage changes smoothly with the shock current wave head time, and the steep wave response is good, without gap breakdown characteristics and arc extinction problems. Its resistors can absorb large energy per unit volume and can also be used in parallel, so it is particularly beneficial to protect EHV long-distance transmission systems and large capacity capacitor banks. It is also suitable for the protection of low-voltage distribution network, which is the main protection measure of low-voltage distribution network.

        When the difference between the tower top potential Ut and the induced potential U1 on the conductor exceeds 50% of the discharge voltage of the insulator string, flashover will occur from the tower top to the conductor. That is, Ut Ul>U50. If the influence of line power frequency voltage amplitude Um is considered. Then it is Ut Ul+Um>U50. Therefore, the lightning withstand level of the line is related to three important factors, namely the 5 ∞ pier voltage of the line insulator, the lightning current intensity and the impulse grounding resistance of the tower body Generally, 50% of the discharge voltage of the line is constant, and the lightning current intensity is related to the geographical location and atmospheric conditions. When the lightning arrester is not installed, the ground resistance of the tower body is often reduced to improve the lightning withstand level of the transmission line. In mountainous areas, it is very difficult to reduce the ground resistance. This is also the reason why the transmission lines are frequently struck by lightning.

        After the installation of lightning arresters, when the transmission line is struck by lightning, the line will spread to the tower. Some of them enter the ground through the tower body. When the lightning current exceeds a certain value, the arrester acts to add shunt. Most of the lightning current flows into the conductor from the arrester and propagates to the adjacent tower. Lightning current flows through the lightning conductor and conductor. Due to the electromagnetic induction between wires, there will be another!} A coupling component is generated between the conductor and the lightning conductor. Because the shunt of the arrester is far greater than the lightning current shunted from the lightning wire, the coupling effect of this shunt will increase the conductor potential, make the potential difference between the conductor and the tower top less than the flashover voltage of the insulator string, and the insulator will not flashover. Therefore, line arrester has good potential clamping effect. This is also the obvious feature of lightning protection of line arrester.

        In the past, the lightning protection of transmission lines mainly adopted the method of reducing the tower grounding resistance. It is relatively easy in plain areas. For tower in mountainous areas, long radiation ground wire or deep well drilling with resistance reducing agent are often used at the four tower feet. To increase the contact area between the ground wire and the soil and reduce the resistivity. The grounding resistance will decrease under power frequency condition. However, in the event of lightning stroke, because the grounding wire is too long, there will be a large additional inductance value. The transient component of lightning overvoltage, Ldi/dt, will be added to the tower body potential, which will greatly increase the tower top potential, more likely to cause the tower body and insulator string flashover, which will reduce the lightning withstand level of the line. Because the line arrester has the potential clamping effect, and the requirements for grounding resistance are not too strict, it is easier to achieve lightning protection for lines in mountainous areas, and the lightning withstand level of lines has changed significantly before and after installing the arrester. It is not difficult to find that the lightning protection effect of adding line arrester is very obvious. Before the arrester is used, its relevant technical parameters should be measured to ensure the installation quality of the arrester.


        Related recommendations

        The online monitoring, distributed fault location and cable online monitoring equipment for power transmission and distribution lines launched by SHENZHEN DINSEE SMART TECHNOLOGY CO.,LTD. has been widely used in Southern Power Grid and State Grid, and has achieved good results.

        Record No.: Yue ICP Bei 2022070794-1 | Website Map XML Map

        主站蜘蛛池模板: 色拍自拍亚洲综合图区| 高潮毛片无遮挡高清视频播放| 国产女精品视频网站免费| 亚洲妇女无套内射精| 亚洲欧美vr色区| 亚洲欧美日韩国产成人一区| 国产又爽又刺激的视频| 强开小婷嫩苞又嫩又紧视频韩国 | 97无码免费人妻超级碰碰夜夜| 成人网站国产在线视频内射视频| 久热这里只精品99国产6-99re视…| 无遮挡啪啪摇乳动态图gif| 国产精品丝袜黑色高跟鞋| 国产乱子伦一区二区三区=| 人妻 色综合网站| 丰满人妻一区二区三区无码av | 久久精品国产99国产精品亚洲| 国产第一页屁屁影院| 动漫精品视频一区二区三区 | 男女裸交免费无遮挡全过程 | 双腿张开被9个男人调教| 久久精品国产曰本波多野结衣 | 国产精品美女久久久久av爽李琼 | 亚洲欧洲中文日韩乱码av| 麻豆精品偷拍人妻在线网址| 国产成人人综合亚洲欧美丁香花| 98国产精品综合一区二区三区 | 少妇午夜福利一区二区| 精品一区二区三区波多野结衣| 99热精品久久只有精品| 高清人人天天夜夜曰狠狠狠狠| 亚洲国产日韩在线人高清| 日本少妇被黑人猛cao| 国产在线精品一区二区三区不卡| 东北女人毛多水多牲交视频| 国产精品久久久久久亚洲影视| 无码日韩av一区二区三区| 欧美人与动欧交视频| av成人午夜无码一区二区| 日韩人妻中文无码一区二区三区| 日日干夜夜操高清视频|